Engineering via SICAM WEB
406
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
9.1.12
Usage of CP-8000/CP-802x as SICAM PAS I/O
The devices CP-8000/CP-802
x
can be used as non-licensed SICAM PAS substations. The
differentiation between normal operation and operation as SICAM PAS I/O is done via a pa-
rameter.
With operation as SICAM PAS I/O, the IEC 60870-5-104 protocol element is defined as a
SICAM PAS I/O interface upon startup. All stations that are connected with this protocol ele-
ment are switched to SICAM PAS I/O mode. A connection with a normally operated station on
the same protocol element is not possible.
Prerequisite for the operation as SICAM PAS I/O is an equipped IEC 60870-5-104 protocol el-
ement (in the following example PRE0 is used).
Set in the directory
SICAM A8000 CP-80xx | Master module | Communication | PRE0
the
parameter project specific settings
to
YES
.
Now appears the directory
SICAM A8000 CP-80xx | Master module | Communication |
PRE0 | project specific settings
. Here you can set the parameter SICAM PAS IO mode to
YES.
For the operation as SICAM PAS I/O the following parameters are relevant:
•
SICAM A8000 CP-80xx | Master module | AU common settings
─
Plant
─
Device name
•
SICAM A8000 CP-80xx | Master module | AU common settings | common address of
ASDU (CASDU)
─
CASDU1
(must be set equally for all data points)
─
CASDU2
(must be set equally for all data points)
•
SICAM A8000 CP-80xx | Master module | Network settings | IP address
─
Own IP address X1/X4
•
SICAM A8000 CP-80xx | Master module | PRE0 | Network connection | LAN | IEC 104
parameter
─
Timeout connection setup t0
─
Timeout transmit t1
─
Timeout transmit acknowledge t2
─
Timeout connection check t3
─
Max. no. of APDUs until acknowledgement (k)
─
number of APDUs until acknowledgement (w)