Preparing the Engineering
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
Unrestricted
249
DC8-037-2.02, Edition 10.2017
7.6
Interfaces for the Communication
CP-8000/CP-802
x
provides the following interfaces for engineering and maintenance:
Interface
Type
Engineering tool
X1
Ethernet TCP/IP
SICAM TOOLBOX II or SICAM WEB
X2
Serial RS-232
*)
SICAM TOOLBOX II or SICAM WEB
X4
Ethernet TCP/IP
SICAM TOOLBOX II or SICAM WEB
X6
Serial RS-232 mode
SICAM WEB
X7
GPRS
SICAM TOOLBOX II or SICAM WEB
*)
with additional voltage output (supply for external modem)
Via the duplicated Ethernet link (X1 and X4 in switch mode) it is for instance possible to con-
nect a local engineering PC and at the same time a GPRS modem for the communication to
the central station.
Furthermore, X1 and X4 can be operated via 2 independent IP addresses, you will find exam-
ples in appendix
,
.
Note
For CP-802
x
applies: X2/pin 3 (supply for external modem) must not be connected with the engineering
PC!
Note
If the serial interface X2 is not used for the engineering, this can be set by means of a special parameter
(
Communication settings serial | Serial engineering interface
=
disabled
).
The engineering via X2 is then no more possible, however, for the connection of other devices (see
) a simpler cable wiring can be created.
7.6.1 Required
Accessories
Depending on the connection type, the following accessories are required:
•
Direct cable
•
D-sub/RJ45 adapter
•
D-sub/USB adapter (if needed)
You will find the order information in appendix