Function Packages
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
Unrestricted
57
DC8-037-2.02, Edition 10.2017
3.1.3
Communication with the Engineering System
(SICAM TOOLBOX II)
For the communication between the SICAM TOOLBOX II and CP-8000/CP-802
x
exist differ-
ent variants:
•
Physical connection
─
Locally by means of a direct cable (RS-232 interface)
─
Remotely
−
Serial communication link via modems (RS-232 or RS-485 interface)
−
Ethernet connection (TCP/IP) and Terminal Server (RS-232 interface)
−
Ethernet connection (TCP/IP)
•
Logical connection of the SICAM TOOLBOX II with that automation unit, that is the subject
of the engineering task:
─
Local automation unit
(that is that one, to which the physical connection exists, regardless in which of the
previously mentioned forms)
─
Remote automation unit
(automation unit that can be reached via the local automation unit; consistent remote
communication according to IEC 60870-5-101 or -104 is required)
Except for first-time initialization processes, all tasks are possible in each of the variants listed
above:
•
Parameter setting
•
Diagnostics
•
Test
•
Load firmware, load parameters
3.1.4
Simplified Engineering via SICAM WEB
For simple engineering tasks a webserver resides on the Master Module. The webserver pro-
vides the menus for the engineering and maintenance designed as websites. The engineering
takes place online via the
Microsoft Internet Explorer ®
.
The following functions are supported:
•
Configuration of I/O Master Module and protocol elements
•
System-technical parameter-setting
•
Diagnosis
•
Event list, alarm list
•
Process display, process simulation
•
Load backup file, save backup file
•
Application program handling (IL)
─
Configuration
─
Load code
─
Diagnosis
─
Online test
Summary of Contents for CP-8000