System Components and Technical Data
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
Unrestricted
115
DC8-037-2.02, Edition 10.2017
•
Clock synchronization according to NTP (Network Time Protocol)
─
NTP server
1)
─
NTP client
1)
─
SNTP client
1)
•
Functions for the support of redundant communication routes
─
Dual LAN interface with integrated switch for ring or star configurations (DNIP)
−
Switch mode
1)
−
Single mode
1)
−
service mode
1)
•
Protocol element control and return information
Protocol element control message
─
START connection to server (“Initiate”)
─
STOP connection to server (“Conclude”)
─
Send (general) interrogation command
─
Preset control location
•
SICAM TOOLBOX II connection over LAN/WAN ("remote connection")
─
Remote connection based on HTTP/HTTPS
1)
─
Authentication in SICAM RTUs using connection password (optional)
1)
─
Warning “Remote Connection”
1)
•
Web Server
─
Integrated web server to display connection-/statistic-/developer information
─
Access to the web server with standard web browser via HTTP
1)
─
Access to the web server with standard web browser via HTTPS
1)
─
Supported web browser
−
Microsoft Internet Explorer 9, 10, 11
−
Microsoft Edge
•
Special functions
─
Conversion of the time information (UTC; local time w/wo Summer-Wintertime)
─
Signaling / measured value disabling
─
Emulation of the going binary information
─
Emulation of the data on reception of the attribute Beh.stVal = "OFF" and
Beh.stVal = “BLOCKED”
─
Technological adaptation for measured values
─
Measured value change monitoring
─
Monitoring intermediate and faulty positions of double-point information
─
Remote parameterization/diagnostic of SICAM RTUs components via IEC 61850
______
1)
function is integrated in the Master Module
2)
not limited (limited only by free memory)
3)
due to performance matters (initialization times upon connection setup), no more than 2000 data
points are recommended
4)
max. startup time (with 10000 data points): approx. 4 min
min. startup time (with 1 data point): approx. 30…60 s (dependent on the configuration of the AU)
5)
supported with restrictions (for details see
SICAM RTUs • Ax 1703 Common Functions Protocol
Elements, chapter “LAN Communication (61850)”, section Basic Data Types” and “Conversion
IEC 60870-5-101/104
↔
IEC 61850“
)
Summary of Contents for CP-8000
Page 604: ......