Engineering via SICAM WEB
434
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Single Command and Double Command
Single commands (TI 45) can be generated by the IL only with the states
0
(OFF) only with
COT
=
7
,
10
(
CON
,
TERM
) and
S
=
1
1
(ON)
Double commands (TI 46) can be generated by the IL only with the states
01
(OFF)
10
(ON)
Other states will not generate a command output.
You find the details for the processing of commands in the manual
SICAM RTUs Common
Functions System and Basic System Elements, chapter "Automation", section "Treatment for
Commands to the Open-/Closed-Loop Control Function according to IEC 60870-5-101/104"
.
9.2.1.7 Generation of Integrated Totals
There are two possibilities of integrated total generation in the control:
•
Spontaneous transmission with change
Automatically if the input address is
unequal
to the output address of the controller.
•
Behavior according to parameter setting of the digital inputs (remote control)
Automatically if the input address is
equal
to the output address of the controller.
9.2.2
Commissioning
and
Test
•
Menu
Home
|
Logic
For commissioning and test of the application program the following functions are available:
•
General functions
─
Import application program
─
Export application program
─
Syntax check
•
Test functions
─
Statistic information
─
Cold restart
─
Warm restart
─
Status of variables
─
Forcing signal inputs