3.2.4 Decentralized
Archive
In case of a communication fault, occurring events can be recorded in a decentralized archive.
After elimination of the fault the superior control system can demand the archive of the re-
spective target system. By means of this function, a possible data loss will be prevented .
•
Reconstruction of all process-relevant data during a communication fault
•
Transmission of the archive to the control system
─
Automatic initiation by the control system
─
File transfer acc. to IEC 60870-5-101, section 7.4.11
•
Data saving
─
Datapoint-specific parameter-settable
─
Number of files, memory size parameter-settable
─
Spontaneous for binary information items and integrated totals
─
Definable cycle for measured values
─
Non-volatile on flash card
•
Configuration acc. to IEC 60870-5-101/104 (point-to-point, multi-point traffic, dial-up traffic,
Ethernet), also multi-hierarchical configurations possible
•
Also multi-hierarchical configurations are possible
•
Reading of the archive via SICAM TOOLBOX II possible
•
Front-end: SICAM AK3, optionally redundant
•
Supported by SICAM 230 (also third-party control system possible)
─
Update of the archive in the control system
─
Own status marking
─
Automatic subsequent billing of
−
Counter differencies
−
Secondary values
−
Mean values and extreme values
3.2.5
Process
Data
Archive
Binary information states, measured values and integrated totals can be recorded in a process
data archive. This archive comprises up to 5.000.000 records over a maximal period of
3 months.
•
Data saving
─
Datapoint-specific parameter-settable
─
Spontaneous for binary information items and integrated totals
─
Definable cycle for measured values
─
Non-volatile on flash card
•
Reading of the archive via SICAM WEB by means of file download possible