Parameter
Value
Test standard
Product standard
Class
Ring waves 100 kHz
normal
2.0 kVp
IEC 61000-4-12
IEC 60870-2-1
>3
Conducted common mode
disturbances common
30…3 V
15 Hz…150 kHz
30 V
16
⅔
/50/60 Hz 60 s
300 V
16
⅔
/50/60 Hz 1 s
IEC 61000-4-16
Voltage ripple DC
10% U
N
IEC 61000-4-17
IEC 60870-2-1
>VR3
Damped oscillotory waves
1 MHz common
2.5 kVp
IEC 61000-4-18
IEC 60870-2-1
4
Damped oscillotory waves
1 MHz normal
2.5 kVp
IEC 61000-4-18
IEC 60870-2-1
>4
Damped oscillotory waves
1 MHz common
2.5 kVp
IEEE C37.90.1
Damped oscillotory waves
1 MHz transverse
2.5 kVp
IEEE C37.90.1
Voltage dips, short-time
interruption and voltage
fluctuations on DC input
connections
Dikps: (
∆
Un)
30% 100ms
30% 500ms
60% 100ms
60% 500ms
Interruptions: (
∆
Un)
100% 10ms
100% 50ms
100% 100ms
100% 500ms
100% 5s
IEC 61000-4-29
IEC60870-2-1
IEC 61850-3 Ed.2
*)
for interruptions/fluctuations > 50 ms applies criterion B: restart of the device allowed
(CP-8000: > 100 ms)