2.1.3 Protocol
Elements
A protocol element serves for the exchange of data – and thus for the transmission of mes-
sages – via a communication interface to other automation units or process control systems.
The hardware for the protocol elements is integrated on the Master Module, and their func-
tionality is provided by means of loadable and parameter-settable firmwares.
Via the communication interfaces the Master Module is able to communicate with an arbitrary
superior or subordinate automation unit in multi-point, point-to-point or dial-up traffic (with the
aid of an external transmission facility), or via LAN/WAN.
2.1.3.1 Supported Protocols
CP-8000/CP-802
x
supports the following protocols and interfaces.
Type
Designation
Interface
Standard protocols
103MT0
IEC 60870-5-103 Master
RS-232, RS-485
BPPT0
IEC 60870-5-101 point-to-point
RS-232, RS-422
DIAST0
Dial-up traffic Slave
RS-232
ET83
IEC 61850 Ed. 1 (Client, Server, GOOSE)
LAN
ET84
IEC 60870-5-104
LAN
ET85
IEC 61850 Ed. 2 (Client, Server, GOOSE), Ed. 1
(Client)
LAN
UMPMT0
IEC 60870-5-101 Master
RS-232, RS-485
UMPST0
IEC 60870-5-101 Slave
RS-232, RS-485
Third-party protocols
AGPMT0
AGP coupling Master
RS-232, RS-485
BMCUT0
Benning MCU ASCII protocol
RS-232, RS-422
COUMT0
IEC 62056-21 (IEC 1107) Master
RS-232, RS-485
DNPST0
DNP3 Slave
RS-232, RS-485
DNPMT0
DNP3 Master
RS-232, RS-485
DNPiT1
DNP3 TCP/IP Slave
LAN
DNPiT2
DNP3 TCP/IP Master
LAN
MODST0
MODBUS RTU Slave
RS-232, RS-485
MODMT2
MODBUS RTU Master
RS-232, RS-485
PCBST0
SAT SK 1703 PCMBA Slave
RS-232, RS-485
RP5UT1
ABB RP570/571 Slave
RS-232, RS-485
SMST0
ASCII protocol for SMS alerting
RS-232
ST1ST0
Siemens SINAUT-ST1 Slave
RS-232, RS-485
TG8ST0
L&G Telegyr 800 Slave
RS-232, RS-485
Additional information on interfacing to third-party systems and further protocols is available
on request.
Summary of Contents for CP-8000