9.1.14.2 Show Alarm List
By selecting the submenu
Alarms
the alarm list is displayed. The display is performed as a
table. The table has only reading rights.
Alarms are recorded chronologically upon a change of state in an alarm buffer. The alarms
are distinguished in 2 classes:
•
Diagnosis alarms (notifications from the diagnosis function)
•
Process alarms (states of signals that are marked as an alarm), refer to
Configurable Logging and Display of Signal States
When selecting the alarm list, all the present alarms are loaded, this means, the table contains
only current states. The states “going” and “off” are not displayed in the table. If a notification
has the state “going” or “off”, the corresponding row disappears.
The table is sorted chronologically descending (latest alarm first, oldest alarm at last). If a new
alarm occurs, this is automatically prepended at the first place of the table. The older alarms
are moved down.
Halt Function
By means of clicking on the button you can halt the display of new alarms. If new alarms
occur, then they are recorded furthermore in the alarm buffer, but not displayed in the table.
Depending on the state the button changes its design:
•
Alarm display halted and no new alarm occurred:
•
Alarm display halted and new alarm occurred:
By means of clicking the green button the current alarms are displayed in the table.
By means of clicking the general button the alarm list is reloaded. With activated halt
function, this is thereby not canceled.