Service
496
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
11.3 Diagnosis
11.3.1 Distinction of the Error Types
The following listing explains the different error types and their logging.
•
System errors
─
Supervision of the system, communication, time synchronization by the firmware of the
configured system elements
−
Logging in the online diagnosis
−
Activation of the red error LED on the Master Module
•
Parameterization errors (telecontrol function)
─
Supervision by the engineering tool
−
Specific conventions or plausibility checks
−
Indication upon entry or prevention of the transfer
─
Supervision online by the firmwares of the configured system elements
−
Logging in the online diagnosis
−
Activation of the red error LED on the Master Module
If in the target device a parameterization is loaded that does not match with the mechani-
cal present system elements, this leads to the indication of a hardware error.
•
Programming errors (
open-/closed-loop control function
)
─
Supervision by CAEx
plus
(engineering via SICAM TOOLBOX II)
−
Specific conventions or plausibility checks
−
Indication upon entry or prevention of the transfer
─
Supervision by the CAEx
plus
compiler (engineering via SICAM TOOLBOX II)
−
Logging in the "Error state viewer"
─
Supervision by the ASCII-Compiler during startup (engineering via SICAM WEB)
−
Logging in the PLC diagnosis
─
Supervision online by the firmware of the Master Module
−
Logging in the online diagnosis
•
Operator errors
Are largely excluded due to plausibility checks or queries by the engineering tool (addi-
tional hints see Appendix
Errors with the Engineering via SICAM WEB
).
Note
Naturally, all operator inputs, such as for example the loading of parameters or the online testing, are
subject to the responsibility of the user.
Profound knowledge of the automation technique in general, as well as the documents mentioned in the
Preface is presumed.
Errors that are recorded in the online diagnosis are devided in diagnosis classes and contain
further indications about the possible error cause, as well as hints for the error elimination
(“cause“, “remedy“).
You find the meaning of the diagnosis classes in the manual
SICAM RTUs Common Func-
tions System and Basic System Elements, chapter „System Services“, section „Diagnostic and
Signaling“
.
You find the error indications recorded in the online diagnosis in the
SICAM TOOLBOX II
Online Help, chapter "Parameter Documentation and Diagnosis Info", section "Diagnosis In-
formation"
, under the respective firmware.