Engineering via SICAM WEB
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
Unrestricted
335
DC8-037-2.02, Edition 10.2017
9.1.5
Configuration of the Time Management
•
Menu
Home | Settings
9.1.5.1 Time Synchronization
The internal clock of CP-8000/CP-802
x
serves for the time tagging of generated data
•
from the periphery
•
from the optional
Open/closed-loop control function
•
for the records in the diagnosis
The resolution of the time tag is 1 ms.
The settings for the time synchronization reside in the directory tree under
SICAM A8000 CP-80xx | Master module | Time management | Common settings
(the checkbox S
HOW ALL PARAMETERS
must be activated).
CP-8000/CP-802
x
supports the following time synchronization variants (selectable with pa-
rameter
Synchronizing of the automation unit
):
•
Remote synchronization via serial communication or via LAN
•
Free running
With the Parameter
Monitoring time for synchroniz. event
the monitoring fort he re-
mote synchronization is defined. If the time was already set and if there is no synchronization
within the parameterized time, a warning is recorded in the diagnosis.
With the Parameter
Unit of time for free running and monitoring time
the unit of
the monitoring time is defined (seconds or minutes).
You find the detailed information on the time synchronization reside in the manual
SICAM
RTUs Common Functions System and Basic System Elements, chapter "System Services",
section "Time Management", section "Time Synchronization"
.