Service
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
Unrestricted
473
DC8-037-2.02, Edition 10.2017
11.1.1 Description of the LED Display
The LED display comprises the operating states
•
LEDs for the system status
•
LEDs for the connection status of the communication interfaces (dependent on the config-
ured protocol elements)
Meaning of the subsequently represented symbols:
Symbol Status
Symbol
Status
˜
Active
(lighting)
§
Flashes
regularly
™
Inactive
(dark)
V
Flashes
irregularly
ž
Flickers (data exchange)
x
Not
relevant
System Status
CP-8000/CP-802
x
Name
Color
Function
LED
Meaning
POK
Green
Power ok
(only CP-8000)
˜
Power supply without error
™
•
Sum error (voltage failure, power supply defective,
etc.)
•
Startup
RY
Yellow
Ready
˜
System ready
§
•
Loading of parameters into the Flash PROM
•
Loading of firmware into the Flash PROM
™
•
System or specific module not ready
V
•
Startup
ER
Red
Error
˜
•
Sum error (internal error, external error, warning,
module failure, system failure; inclusive I/O Master
Module)
•
Startup
™
No error
PS-862
x
/PS-864
x
Name
Color
Function
LED
Meaning
RY
Yellow
Ready
˜
Module ready
§
•
1 s interval: PS in boot loader (startup)
•
0.3 s interval: Connection to CP-802
x
interrupted
•
0.1 s interval: Loading of firmware into the Flash
PROM
™
•
Sum error (voltage failure, power supply defective,
at least one of the monitored voltages smaller than
setpoint value)
•
Startup
Summary of Contents for CP-8000