Engineering via SICAM WEB
392
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Processing type
Parameter
Meaning
transformer_type
Transformer type
transformer_angle
Angle between upper and lower side of trans-
former
0 to 359
Overrange
Definition of the overrange for QDS 'OV' in %
of the nominal range of the transformer
9.1.11.4.5 Parameters with Assignment on the AO Module
Processing type
Parameter
Meaning
AO_I – analog output
current
fail_subst value
Substitute value, if behavior of failure is
parametrized on ouput substitute value (S)
-1000000000000000.000 to
1000000000000000.000
select_execute_t
Max. time between select and execute (in
seconds). After this time a recent select com-
mand is necessary. 0 = no select command is
expected (direct command transmission)
0 to 6553.5
Fail_behav
Behavior at failure
•
Keep
•
Substitute value
block
Blocking (=not used) (S)
NO/YES
X_0%
Nominal range in the physical unit of the
input/output (0%) (S)
-20.0 to 20.0
X_100%
Nominal range in the physical unit of the
input/output (100%)
-20.0 to 20.0
Y_0%
Technological or normalized value 0% (S)
-1000000000000000.000 to
1000000000000000.000
Y_100%
Technological or normalized value 100% (S)
-1000000000000000.000 to
1000000000000000.000
receive format
Source of datapoint
spontaneous
termination_t
Time between confirmation and termination (s)
0 = no termination
0 to 6553.5
SID-BSE
Source identification basic system element
SID-ST
Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254; if
automatic, the SID will be learned
SID-SSE
Source identification supplementary system
element
AO_U – analog output
voltage
fail_subst value
Substitute value, if behavior of failure is
parametrized on ouput substitute value (S)
-1000000000000000.000 to
Summary of Contents for CP-8000