Engineering via SICAM WEB
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
Unrestricted
343
DC8-037-2.02, Edition 10.2017
9.1.7.4 Settings of the Messages
The settings of the messages reside in the directory tree under
SICAM A8000 CP-80xx | Master module | Communication | PRE
<0…3>
| IEC60870-5-
101/104
(the checkbox S
HOW ALL PARAMETERS
must be activated).
These settings are independent on the communication type and exist on the Master Module
individually for each protocol element:
•
Transmission with/without time tag
•
Variable elements of the message
•
Command time monitoring
•
Monitoring ACTCON
Transmission with/without time tag
The information objects supported by CP-8000/CP-802
x
can be transmitted to the control cen-
ter either with time tag or without time tag. The definition happens selectively for each type
identification.
You find the parameters thereto in the subdirectory
Transmission with/without time tag
.
Variable elements of the message
For the communication with different systems the byte numbers of the identifiers in the mes-
sage header can be parameterized.
The settings on the Master Module reside in the subdirectory under
Varia-
ble elements of the message
.
You find the information thereto in the manual
SICAM RTUs Common Functions System and
Basic System Elements, Appendix "Message Formats"
.
The settings on the protocol element reside in the directory tree under
SICAM A8000 CP-80xx | Master module | PRE
<0…3>
:
<protocol >
| Advanced settings |
IEC 60870-5-101
(applies only for point-to-point traffic and multi-point traffic).
You find the information thereto in the manual
SICAM RTUs Common Functions Protocol El-
ements, chapter "Multi-Point Traffic (UMP)", section "Communication according to
IEC 60870-5-101", "Data Acquisition by Polling (Station Interrogation)"
.