Engineering via SICAM WEB
364
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Category
Parameter
Meaning
PRE_(RED)
Protocol element number
Priority_(RED)
Priority 0 (lowest)…priority 14 (highest)
SID-BSE
Source identification basic system element
SID-ST
Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254; if
automatic, the SID will be learned
SID-SSE
Source identification supplementary system
element
Redundancy return in-
formation message
Return_information_function_
(RED)
•
Redundancy state
•
Switchover runs at a global switchover
•
Keyswitch of the SCA-RS: system A active
•
Keyswitch of the SCA-RS: automatic
•
Keyswitch of the SCA-RS: system B active
•
Listening mode
BSE_(RED)
Basic system element
PRE_(RED)
Protocol element number
Selective data flow rout-
ing
PRE
Protocol element number (0…3)
Station
0…99 = selective station
unused = single-point-PRE or multi-point-
PRE to all remote stations
Data_class
•
Data class 1
•
Data class 2
Periodical transfer
Selection periodical level or no periodical
transfer
Event_data
Time_tag
Transfer with or without time tag
Function_group
address-conversion
0 = yes, 1 = no
Change_sign_of_measured_
values
New_CASDU1
New address of the datapoint. The complete
address consists of new CASDU1, CASDU2,
IOA1, IOA2 and IOA3. New CASDU1 and
CASDU2 = 255 means no address-
conversion.
New_CASDU2
New address of the datapoint. The complete
address consists of new CASDU1, CASDU2,
IOA1, IOA2 and IOA3. New CASDU1 and
CASDU2 = 255 means no address-
conversion.
New_IOA1
New address of the datapoint. The complete
address consists of new CASDU1, CASDU2,
IOA1, IOA2 and IOA3. New CASDU1 and
CASDU2 = 255 means no address-
conversion.
New_IOA2
New address of the datapoint. The complete
address consists of new CASDU1, CASDU2,
IOA1, IOA2 and IOA3. New CASDU1 and
CASDU2 = 255 means no address-
conversion.
Summary of Contents for CP-8000