Engineering via SICAM WEB
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
Unrestricted
461
DC8-037-2.02, Edition 10.2017
Signals for the SICAM PAS coupling
Process-technical settings
Signal
DIGITAL_VALUE, DIGITAL_VALUE_TYPE = SINGLE
TI 30
DIGITAL_VALUE, DIGITAL_VALUE_TYPE = DOUBLE
TI 31
ANALOG_VALUE, ANALOG_VALUE_TYPE = NORMALIZED
TI 34
ANALOG_VALUE, ANALOG_VALUE_TYPE = SCALED
TI 35
ANALOG_VALUE, ANALOG_VALUE_TYPE = FLOAT
TI 36
COUNTER_VALUE
TI 37
DIGITAL_CONTROL, DIGITAL_CONTROL_TYPE = SINGLE
TI 45
DIGITAL_CONTROL, DIGITAL_CONTROL_TYPE = DOUBLE
TI 46
ANALOG_CONTROL, ANALOG_CONTROL_TYPE = NORMALIZED
TI 48
ANALOG_CONTROL, ANALOG_CONTROL_TYPE = SCALED
TI 49
ANALOG_CONTROL, ANALOG_CONTROL_TYPE = FLOAT
TI 50
OUTPUT_TIME0
1)
OUTPUT_TIME1
2)
OUTPUT_TIME2
3)
TI 45, TI 46, TI 47
TELEGRAM_ADDRESS
(IOA3 x 65536) +
(IOA2 x 256) + IOA1
HIERARCHICAL_NAME
Signal name if available, else
CASDU
_<casdu>
_IOA_
<ioa>
DIGITAL_CONTROL, DIGITAL_CONTROL_TYPE = SINGLE
TI 45
1)
single
command:
Output_t
, double command:
output_t0
,
output_t1
2)
AU common settings | Short pulse duration
3)
AU common settings | Long pulse duration
9.3.6
Download Process Data Archive
The data which is stored in the process data archive can be downloaded as CSV file and be
stored on the engineering PC. This file can be subsequently read as a table.
The file contains those binary information items, measured values and integrated totals, that
have been parameterized for the record in the process data archive (see
,
rable Logging and Display of Signal States
).
Select thereto the submenu
Download process data archive
.
The following dialog will appear: