Engineering via SICAM WEB
390
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Processing type
Parameter
Meaning
SW_CT_FDIR_I>_I>>
I>
Trip value in ampere for overcurrent detection
for short circuit 0: function disabled
50 to 2000
I>>
Trip value in ampere for overcurrent detection
for short circuit 0: function disabled
50 to 2000
I>>_t
Time delay for overcurrent detection
0.04 to 60
I>_t
Time delay for overcurrent detection
0.04 to 60
t_reset
Auto reset time
0 = function disabled
SW_CT_FDIR_IN
IN>
Trip value in ampere for ground fault 0: func-
tion disabled
0.4 to 2000
IN>_Idir
Earth current for earth fault detection using
the wattmetric method 0: function disabled
0.2 to 30
IN>_ground_type
Ground point treatment method
•
Solid
•
Isolated
•
Resonant
IN>_U0
Ground point displacement voltage in procent
of primary voltage 0: function disabled
0 to 100
IN>_U0_t
Ground point displacement voltage time delay
0.04 to 60
IN>_t
Time delay for ground fault indication
0.04 to 60
t_reset
Auto reset time
0 = function disabled
SW_CT_MV_SELECTIO
N
measured_value_selection
Selection of a measured value
thresh_additive
Change threshold in % of X_100% (S) AI_T:
% of temperature range
0 to 1000.0
thresh_uncond
Change threshold in % of X_100% (S) AI_T:
% of temperature range
0 to 103.00
SW_CT_PDIR
–
SW_F – software fre-
quency
thresh_additive
Change threshold in % of X_100% (S) AI_T:
% of temperature range
0 to 1000.0
thresh_uncond
Change threshold in % of X_100% (S) AI_T:
% of temperature range
0 to 103.00
SW_PQ - software power
thresh_additive
Change threshold in % of X_100% (S) AI_T:
% of temperature range
0 to 1000.0
thresh_uncond
Change threshold in % of X_100% (S) AI_T:
% of temperature range
0 to 103.00