Engineering via SICAM WEB
346
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Recording Grid for Measured Values
This parameter defines the recording grid (the cycle time) for measured values. It can be set
from 1 to 60 minutes.
Timeout for Filetransfer
With this parameter it is defined when the data transmission will be cancelled if a disturbance
occurs during a file transfer (connection error etc.).
Number of Bytes for CASDU, IOA, COT in the Archive
You can select the format of saving the entries into the archive. If there is a control system
which needs another format for the CASDU, IOA or COT you can define this with the help of
these parameters. The parameters only affect the entries in the archive, however, it will not af-
fect any other data in your automation unit.
Note
It is not possible to call the archive from more than one different control system which use different set-
tings for the number of bytes for CASDU, IOA, COT, because the settings for these parameters affect the
whole archive of a automation unit.
Spontaneous Transmission of Directory List
It is possible to transmit the directory list spontaneously. This behavior is specified in the
IEC 60870-5. It means, that whenever there is a change in the directory list (one file was writ-
ten, or an old file was deleted), this change may be reported to the control system. However,
since upon initialization of a file transfer the control system asks for the directory list anyway, it
is not useful to transmit the directory list spontaneously.
Note
The addresses that are calculated automatically are not shown in the web browser. If such an address is
set in the parameterization of the telecontrol function, an error message occurs on attempt to apply.