Engineering via SICAM WEB
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
Unrestricted
409
DC8-037-2.02, Edition 10.2017
9.1.13.1.1 Supported Signal Types
Processing type
Type identification
Signal inputs
DI_SI
Single-point information (TI 30)
DI_DI
Double-point information (TI 31)
DI_CV
Counter value (TI 37)
DI_CV_Sub
Counter value (TI 37)
AI_I
Measured value normalized (TI 34)
Measured value scaled (TI 35)
Measured value short floating point (TI 36)
AI_U
Measured value normalized (TI 34)
Measured value scaled (TI 35)
Measured value short floating point (TI 36)
AI_T
Measured value normalized (TI 34)
Measured value scaled (TI 35)
Measured value short floating point (TI 36)
T_AI_I (CTVT)
Measured value normalized (TI 34)
Measured value scaled (TI 35)
Measured value short floating point (TI 36)
T_AI_U (CTVT)
Measured value normalized (TI 34)
Measured value scaled (TI 35)
Measured value short floating point (TI 36)
Signal outputs
DO_SI
Single-point information (TI 30)
DO_SX
Single-point information (TI 30)
Single command (TI 45)
DO_DX
Single command (TI 45)
Double command (TI 46)
DO_SC_1POL
Single command (TI 45)
DO_SC_1.5POL
Single command (TI 45)
DO_SC_2POL
Single command (TI 45)
DO_DC_1POL
Single command (TI 45)
Double command (TI 46)
Tap positioning command (TI 47)
DO_DC_1.5POL
Single command (TI 45)
Double command (TI 46)
Tap positioning command (TI 47)
DO_DC_2POL
Single command (TI 45)
Double command (TI 46)
Tap positioning command (TI 47)
AO_I
Measured value normed (TI 34)
Measured value scaled (TI 35)
Measured value short floating point (TI 36)
Setpoint normed (TI 48)
Setpoint scaled (TI 49)
Setpoint short floating point (TI 50)
AO_U
Measured value normed (TI 34)
Measured value scaled (TI 35)
Measured value short floating point (TI 36)
Setpoint normed (TI 48)
Setpoint scaled (TI 49)
Setpoint short floating point (TI 50)