Ambient Conditions
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
Unrestricted
85
DC8-037-2.02, Edition 10.2017
4.4.7
Communication with Insulation: LAN
Parameter
Value
Test standard
Product stand.
Class
Dielectrical test (50 Hz)
U
≤
DC 70 V/AC 33 V
1.5 kV
eff
60 s
IEC 60255-27
IEC 60870-2-1
>VW2
Impulse voltage 1.2/50
µ
s
common
2.5 kVp
IEC 60255-27
IEC 60870-2-1
>VW2
Impulse voltage 1.2/50
µ
s
normal
2.5 kVp
IEC 60255-27
IEC 60870-2-1
>VW2
Fast transient burst
common
4.0 kVp 5 kHz
*)
IEC 61000-4-4
IEC 60870-2-1
3
Fast transient burst
normal
4.0 kVp
IEEE C37.90.1
Surge 1.2/50µs
common
2.0 kVp
IEC 61000-4-5
IEC 60870-2-1
3
Surge 1.2/50µs
normal
2.0 kVp
IEC 61000-4-5
IEC 60870-2-1
3
Conducted disturbances
(induced HF)
10 V 0.15…80 MHz
80% AM 1 kHz
IEC 61000-4-6
IEC 61850-3
Ring waves 100 kHz
common
2.0 kVp
IEC 61000-4-12
IEC 60870-2-1
4
Ring waves 100 kHz
normal
2.0 kVp
IEC 61000-4-12
IEC 60870-2-1
4
Conducted common mode
disturbances common
30…3 V
15 Hz…150 kHz
30 V
16
⅔
/50/60 Hz 60 s
300 V
16
⅔
/50/60 Hz 1 s
IEC 61000-4-16
IEC 61850-3 Ed.2
Damped oscillatory waves
1 MHz common
2.5 kVp
IEC 61000-4-18
IEC 60870-2-1
4
Damped oscillatory waves
1 MHz common
2.5 kVp
IEEE C37.90.1
*)
CP-8000: tested with 2.0 kVp
The listed values are valid for shielded cat.5 cables with a length of up to 100 m.