Preparing the Engineering
264
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
7.7.2.2.2 Point-to-Point Connection via Ethernet Interface
The following steps are necessary:
•
Configure IP address for engineering PC
•
Connection setup via SICAM WEB
Configure IP Address for Engineering PC
For the parameter setting the engineering PC must be adjusted corresponding to the IP ad-
dress predefined in CP-8000/CP-802
x
.
•
Click in the control panel of the engineering PC on
Network connections
, after that on
Local Network
and
Properties
.
•
Mark in the property dialog
Internet Protocol (TCP/IP)
and click on
Properties
.
•
Select
U
SE THE FOLLOW ING
IP
ADDRESS
: and enter for instance
172.16.0.4
and the
subnet mask
255.255.0.0
, and confirm with
OK
.
•
Confirm the network setings with
OK
.
Connection via SICAM WEB
Start the web browser and enter the IP address of your target device (
172.16.0.3
) in the
address bar.
You find the further information in chapter
.
Note
According to the parameterization in CP-8000/CP-802
x
you have to enter a http or https address in the
browser to establish the connection.
During the first time connetion establishment via https there is a check if the corresponding security certifi-
cate is installed. If it is missing, it must be installed manually (see
, tab
Cyber Security General Downloads
, directory
Application Notes
, document
Certificate trusting in
web browsers
).