Engineering via SICAM WEB
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
Unrestricted
365
DC8-037-2.02, Edition 10.2017
Category
Parameter
Meaning
New_IOA3
New address of the datapoint. The complete
address consists of new CASDU1, CASDU2,
IOA1, IOA2 and IOA3. New CASDU1 and
CASDU2 = 255 means no address-
conversion.
Selectivity
Selective or to all remote stations
SID-BSE
Source identification basic system element
SID-ST
Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254; if
automatic, the SID will be learned
SID-SSE
Source identification supplementary system
element
Special application input
OUT_CASDU1
Address of the datapoint
OUT_CASDU2
Address of the datapoint
OUT_IOA1
Address of the datapoint
OUT_IOA2
Address of the datapoint
OUT_IOA3
Address of the datapoint
OUT_TI
Type identification according to
IEC 60870-5-101/104
Inversion
NO/YES
TI31_Selection
OFF/ON
Fail_behav
Failure behavior
Fail_subst_value
Substitute value at failure
single_object_number
Command_state
•
Command state not evaluate
•
Command state ON before OFF
•
Command state OFF before ON
Command_output_time
For TI 160: 0...6200•50 ms, for TI 45, 46, 47:
•
0=no additional definition
•
1=short pulse duration
•
2=long pule duration
•
3=persistent output
SID-BSE
Source identification basic system element
SID-ST
Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254; if
automatic, the SID will be learned
SID-SSE
Source identification supplementary system
element
Special application output Function
•
OR conjunction, falling edge time delayed
•
AND conjunction, falling edge time delayed
•
OR conjunction, output as transients, falling
edge time delayed
•
Message conversion
•
OR conjunction, rising edge time delayed
Inversion
NO/YES
Fail_behav_status
Conjunction type
Time_delay
Time delay n•100 ms
•
0 0 no delay
•
1 = 100 ms
•
255 = 25.5 s