System Components and Technical Data
162
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
5.7.3.8 DO-6220, DO-6221, DO-6230
5.7.3.8.1 Functions
•
Pulse commands
t1
─
Checked output of pulse commands
−
1-pole, 1½-pole, 2-pole
−
Cannot be mixed on one module
─
Single, double and regulating step commands
─
Application functions and procedures according to IEC 60870-5-101/104
−
Formal check
−
Direct command
−
Select and execute command ("select/execute")
─
Control location check
─
Retry suppression
─
1-out-of-n check
─
Command locking
─
Synchronization
─
Revision
─
DO-6220 - command output according to IC1
−
Idle check
−
Selective activation check
─
DO-6221 - command output according to RC1
−
Idle check
−
Selective activation check
−
Resistance check
−
Current flow information
−
Earth fault check
−
Interference voltage check
─
Command output time
−
Settable
−
Dependent on the process
─
Return information monitoring
─
Command prolongation
─
Periodical control circuit check
─
Switching sequences
─
Monitoring of command output sequence to prevent incorrect outputs
─
Command initionation for auto-reclose
─
Activation of command contactors with or without series-break contacts (with DO-6221)
•
Return information to pulse command assignment (applies for DO-6230)
─
Settable assignment for messages and pulse commands, which are acquired or output
on the I/O Master Module
─
Predefined assignment for messages and pulse commands, which are acquired or
output on the I/O Master Module
Summary of Contents for CP-8000