Function Packages
68
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
3.3
Automation
The function package
Automation
contains the following functions:
•
Telecontrol interface
─
Reception of messages with process information
─
Handling of commands according to IEC 60870-5-101/104
─
Change management and generation of messages with time tag
•
Open-/closed-loop control function
─
Test functions
•
Process data input and output
3.3.1 Telecontrol
Interface
3.3.1.1 Transfer of Messages with Process Information
Reception of
messages with process information
and transfer to the
open-/closed-loop control func-
tion
for the purpose of further processing.
Messages with process information
in monitor direction:
•
Single-point information, double-point information, step position information
•
Measured values
•
Integrated totals
•
Bitstring of 32 bit
Messages with process information
in control direction:
•
Single commands, double commands, regulating step commands
•
Setpoint commands
•
Bitstring of 32 bit
3.3.1.1.1 Treatment for Commands According to IEC 60870-101/104
The treatment for commands serves for the check of the spontaneous information objects to
be processed with the help of the
open-/closed loop control function
and transmission of the con-
firmation for:
•
Pulse commands (single commands, double commands, regulating step commands)
•
Setpoint values (setpoint command)
•
Bitstring of 32 bit
The data transfer of the spontaneous information objects to the
open-/closed-loop control func-
tion
for further processing is dependent on the result of the checks.
Summary of Contents for CP-8000