Communication parameter group 07
PARAMETER DESCRIPTION 113
5.8 Communication parameter group 07
Group
Parameter
number
Name
Setting range
Default Page
07-00
P.33
Communication protocol
selection
0:Modbus protocol
1
1:Shihlin protocol
07-01
P.36
Inverter communication
station number
0~254
0
07-02
P.32
Serial communication baud
rate
0:
baud rate
:4800bps
1
1:
baud rate
:9600bps
2:
baud rate
:19200bps
3:
baud rate
:38400bps
07-03
P.48
Data length
0:8bit
0
1:7bit
07-04
P.49
Stop bit length
0:1bit
0
1:2bit
07-05
P.50
Parity check selection
0:No parity check
0
1:Odd
2:Even
07-06
P.51
CR/LF selection
1:CR only
1
2:Both CR and LF
07-07
P.154
Modbus communication
format
0:1、7、N、2 (Modbus, ASCII)
4
1:1、7、E、1 (Modbus, ASCII)
2:1、7、O、1 (Modbus, ASCII)
3:1、8、N、2 (Modbus, RTU)
4:1、8、E、1 (Modbus, RTU)
5:1、8、O、1 (Modbus, RTU)
6:1、8、N、1 (Modbus, RTU)
07-08
P.52
Number of communication
retries
0~10
1
07-09
P.53
Communication interval
allowed time
0~999.8s:Check communication timeout with the
set value
99999
99999:No timeout check
07-10
P.153
Communication alarm action
0:Alarm and stop freely
1
1:No alarm and continuing to operation
07-11
P.34
Communication EEPROM
write-in selection
0:When writing parameters in communication
mode, write in RAM and EEPROM
0
1:When writing parameters
through
communication, only write into RAM