System parameter group 00
PARAMETER DESCRIPTION 55
5.1.8 Stop operation selection
Select the inverter stop method
Parameter
Name
Default Setting Range
Content
00-13
P.71
Idling brake / DC
brake
1
0
Idling brake
1
DC brake
00-14
P.75
function
selection
1
0
Press
button and inverter stop running in PU and
H2(combine mode 2) mode
1
Press
button and inverter stop running in all mode.
Idling brake / DC brake
Idling brake(00-13(P.71)=“0”)
After receiving stop signal, inverter stops output immediately, and the motor idle freely.
ON
OFF
Run signal
Time
O
ut
pu
t f
re
qu
en
cy
(H
z)
Motor idle freely
DC braking(00-13(P.71)=“1”)
After receiving stop signal, inverter decelerates according to the acceleration/deceleration curve until it stops
completely.
Time
O
ut
pu
t f
re
qu
en
cy
(H
z)
ON
OFF
Run signal
Deceleration time
(set by 01-07(P.8))
DC brake
button function selection
Press
button to stop during operation (00-14(P.75)=“1”)
Note:
When running in non-PU and H2 modes, pressing the
button will display E0 and lock all
functions on the keypad. Please follow the steps below to cancel this state
:
1. If the start signal is given from digital input terminal, switch off the signal (Note1);
2.
Press
button for over 1.0 second to remove E0 state.
Note: In programmed operation mode, it is not necessary to switch off the start signal. Inverter will run at the section
where it stopped after reset.
Setting
Setting