Motor parameter group 05
PARAMETER DESCRIPTION 105
5.6.1 Motor parameter
Inverter has built-in standard parameters for motor. Modify the default values according to the actual situation to
conform to the actual values as much as possible.
Parameter
Name
Default
Setting Range
Content
05-01
P.302
Motor rated power
0.00kW
0~160kW
---
05-02
P.303
Motor poles
4
0~48
---
05-03
P.304
Motor rated voltage
380V/440V
0~510V
440V 50Hz/60Hz system
220V
220V system
05-04
P.305
Motor rated frequency
50.00Hz
0~599.00Hz
50Hz system (when 00-24(P.189)=1)
60.00Hz
60Hz system (when 00-24(P.189)=0)
05-05
P.306
Motor rated current
According
to kW
0~500.00A
05-06
P.307
Motor rated rotation
speed
1410r/min
0~9998r/min
50Hz system (when 00-24(P.189)=1)
1710r/min
60Hz system (when 00-24(P.189)=0)
05-07
P.308
Motor excitation
current
According
to kW
0~500.00A
05-08
P.309
IM motor stator
resistance
According
to kW
0~99.98Ω
Motor parameter
The user needs to write the motor parameters correctly according to the motor nameplate.
Note:1. When inverter is used with different size motor, please be sure to set parameters 05-01~05-06(P.302~P.307)。
2.
If one or more parameter values in 05-01~05-08(P.302~P.309) have been manually modified, reset the inverter
to reload the new parameter values.