Appendix 1 Parameter table
Appendix 163
Parameter
Number
Group
Name
Setting Range
Default
Page
P.77
00-03
Selection of parameters
write protection
0: Parameters can be written only when the motor
stops.
0
1: Parameters cannot be written.
2: Parameters can also be written when the motor is
running.
3: Parameters cannot be read when in password
protection.
P.78
00-15
Prevent forward/reverse
rotation selection
0: Forward/reverse rotation are both permitted.
0
1: Prevent reverse rotation (Giving reverse signal
decelerates and stops the motor).
2: Prevent forward rotation (Giving forward signal
decelerates and stops the motor).
P.79
00-16
Operation mode selection
0: “PU mode”, “external mode” and “Jog mode” are
interchangeable.
0
1: “PU mode” and “JOG mode” are interchangeable.
2: “External mode” only
3: “Communication mode” only
4: “Combined mode 1”
5: “Combined mode 2”
6: “Combined mode 3”
7: “Combined mode 4”
8: “Combined mode 5”
P.80
03-03
Terminal M0 input
function
Same as 03-00
2
P.81
03-04
Terminal M1 input
function
Same as 03-00
3
P.83
03-00
Terminal STF input
function
0: STF(Inverter runs forward)
0
1: STR(Inverter runs reverse)
2: RL(Multi-speed low speed)
3: RM(Multi-speed medium speed)
4: RH(Multi-speed high speed)
5: Reserved
6: External thermal relay actuate
7: MRS(Stops inverter output immediately)
8: RT(Inverter second function)
9: EXT(External JOG)
10:STF+EXJ
11:STR+EXJ
12:STF+RT
13:STR+RT
14:STF+RL
15:STR+RL