Analog input and output parameter group 02
PARAMETER DESCRIPTION 78
5.3.2 Auxiliary frequency
Frequency can be adjusted and synthesized flexibly to meet the different control requirements in different
scenarios.
Parameter
Name
Default Setting Range
Content
02-07
P.240
Auxiliary frequency
0
0
Off
2
Output frequency = basic fre auxiliary frequency
(given by terminal 3-5)
4
Output frequency = basic frequency - auxiliary frequency
(given by terminal 3-5)
6
Output frequency = proportional linkage signal (given by
terminal 3-5)
Auxiliary frequency
When output frequency is lower than 01-01(P.2),it equals to lower limit frequency 01-01(P.2).
When output
frequency is higher than 01-00(P.1), it equals to upper limit frequency 01-00(P.1).
Note: 1.Basic frequency command is given by keypad, communication or multi-speed terminal.
2. For proportional linkage signals, please refer to the description of parameter 02-06(P.185).
3. When use terminal 3-5
analog (voltage/current) signal as proportional linkage signal input terminal, please refer
to parameter 02-20(P.17).
For the setting of external analog signal frequency range, please refer to parameter
02-21(P.39).
Setting
Summary of Contents for SL3 Series
Page 2: ......
Page 107: ......
Page 200: ...Appendix 4 Optional equipment Appendix 196 ...
Page 210: ...Appendix 5 European Specification Compatibility Description Appendix 206 ...