Application parameter group 10
PARAMETER DESCRIPTION 140
5.10.4 Restart mode selection
Select suitable start mode according to different load conditions.
Parameter
Name
Default Setting Range
Content
10-08
P.150
Restart mode selection
0
x0
No frequency search.
x1
Reserved
x2
Decrease voltage mode
0x
Power on once.
1x
Start each time.
2x
Only instantaneous stop and restart
10-09
P.57
Restart idling time
99999
0~30.0s
---
99999
Off.
10-10
P.58
Restart rising time
10.0s
0~60.0s
Restart mode selection
10-08(P.150) is set by 2 bits. The meaning of each bit is as follows:
10-08
(
P.150
)
=
0
:No frequency search.
1:Reserved
2:Decrease voltage
mode
0
:Power on once.
1:Start each time.
2:Only instantaneous
stop and restart
During motor operation, when instantaneous power interruption occur inverter will stop output immediately. If
10-09(P.57)=99999, inverter will not restart automatically after power is restored; If 10-09(P.57)=0.1~30, when
power is restored, inverter will automatically restart the motor after idling for a period of time (10-09(P.57) value).
When restarting the motor automatically, output frequency is target frequency, but output voltage is zero and then
slowly rises to the proper voltage value. This voltage rise time is called “Restart rising time (10-10(P.58))”.
Instantaneous (power failure) time
Power supply
(R/L1
,
S/L2
,
T/L3)
Motor speed N
(r/min)
Inverter output
frequency f (Hz)
Inverter output
voltage E (v)
Restart cushion time
10-10(P.58) setting
Coasting time 10-
09(P.57)setting
*
* The output shut off timing differs
according to the load condtion
Time
Time
Time
Time
Note:1. 10-08(P.150) must also be set if need instant restart function.
2. If 10-08(P.150) is not 0, in default inverter do linear acceleration and deceleration.