Appendix 1 Parameter table
Appendix 187
Group
Parameter
Number
Name
Setting Range
Default Page
08-19
P.224
Analog feedback signal
gain
0~100.0%
100.0%
08-43
P.251
PID pressure range (Bar)
setting
1.0~100.0
100.0
08-45
P.253
Analog signal feedback
loss detection time
0~600.0
0.0 s
08-46
P.254
Analog signal feedback
loss action selection
0:Alarm AErr and inverter stop freely
0
1:Slow down to stop then alarm AErr
2:Alarm AErr and continue operation
10-00
P.10
DC brake operating
frequency
0~120.00Hz
3.00Hz
10-01
P.11
DC brake operating time
0~60.0s
0.5s
10-02
P.12
DC brake operating
voltage
0~30.0%
4.0%
10-03
P.151
Zero-speed control
function selection
0: Off.
0
1: DC voltage braking
10-04
P.152
Voltage at zero-speed
control
0~30.0%
5.0%
10-05
P.242
DC brake before inverter
start
0: Off
0
1: Before starting operate DC brake first.
10-06
P.243
DC brake time before
inverter start
0~60.0s
0.5s
10-07
P.244
DC brake voltage before
inverter start
0~30.0%
4.0%
10-08
P.150
Restart mode selection
X0:No frequency search.
0
X1:Reserved
X2:Decrease voltage mode
0X:Power on once.
1X:Start each time.
2X:Only instantaneous stop and restart
10-09
P.57
Restart idling time
0~30.0s
99999
99999: Off.
10-10
P.58
Restart rising time
0~60.0s
10.0s
10-11
P.61
Remote control function
0: Off
0
X1:Remote control function, frequency save in memory
X2:Remote control function, frequency won’t save
X3:Remote control function, frequency won’t save, clear
frequency setting every time STF/STR “turn off”.
X4:Remote control function, frequency save in memory
every 5s
1X:Frequency command range 01-01(P.2)~01-00(P.1),
frequency command value from RH,RM setting