PID parameter group 08
PARAMETER DESCRIPTION 135
After increasing the proportional gain, if the output response is still slow, increase the differential gain;
If the output is unstable, reduce the differential gain (KD=08-06(P.174)).
Note: 1. When 08-09(P.177)=2, there is no alarm display on the keypad, multi-function digital output terminal output a
signal. After the inverter stops, the
digital output terminal is automatically off.
5.9.3 PID pressure range setting
Set the range of PID target and feedback.
Parameter
Name
Default Setting Range
Content
08-43
P.251
PID pressure range
(Bar) setting
100.0
1.0~100.0
Set the range of PID target and feedback
PID pressure range
The setting of the PID target value can be %, bar, Kg, etc.
Set 08-43 (P.251) if need the setting of the PID target
value corresponds to the dimension of the actual system, generally set as feedback system sensor range.
For example: If the pressure sensor feedback range is 0~10V, the corresponding pressure range is 0~16.0bar,
then 08-43 (P.251) set 16.0, and 08-03 (P.225)=8.0, then 00- 07 (P.161) = 3 (monitor target pressure) monitoring
is: 8.0.
5.9.4 PID
analog signal feedback loss
Used to detect whether the PID feedback is disconnected.
Parameter
Name
Default Setting Range
Content
08-45
P.253
Analog signal feedback
loss detection time
0.0
s
0.0~600.0 s
Set the time of feedback disconnect detection, set to 0 to
turn off the function
08-46
P.254
Analog signal feedback
loss action selection
0
0
Alarm AErr and inverter stop freely
1
Slow down to stop then alarm AErr
2
Alarm AErr and continue operation
PID disconnection function
Set 08-45 (P.253) to a non-zero value, when inverter is running, PID feedback disconnect exceeds the time set in
08-45 (P.253), inverter react as action set in 08-46 (P.254).
Set 08-45 (P.253) to 0, the feedback disconnection detection function is off.
Note: This function is only suitable for 4-20mA terminal 3-5 signal type.
Setting
Setting