Digital input/ output parameter group 03
PARAMETER DESCRIPTION 88
5.4.1
Digital input terminals function selection
Use the following parameters to change the digital input terminal functions. Each terminal may choose any
function between 0~45 (Note 1)
Parameter
Name
Default Setting Range
Content
03-00
P.83
Terminal STF input
function
0
0
STF(Inverter runs forward)
1
STR(Inverter runs reverse)
2
RL(Multi-speed low speed)
3
RM(Multi-speed medium speed)
4
RH(Multi-speed high speed)
5
Reserved
6
External thermal relay actuate
7
MRS(Stops inverter output immediately)
8
RT(Inverter second function)
9
EXT(External JOG)
10
STF+EXJ
11
STR+EXJ
12
STF+RT
13
STR+RT
14
STF+RL
15
STR+RL
16
STF+RM
17
STR+RM
18
STF+RH
19
STR+RH
20
STF+RL+RM
21
STR+RL+RM
22
STF+RT+RL
23
STR+RT+RL
24
STF+RT+RM
25
STR+RT+RM
26
STF+RT+RL+RM
27
STR+RT+RL+RM
28
RUN(Inverter runs forward)
29
STF/STR(use with RUN signal, when ON, motor runs
reverse; when OFF, motor runs forward)
30
RES(External reset function)
31
STOP(Use as three line control with RUN signal and
STF-STR signal)
32
REX(Extend multi-speed to 16 levels)
33
PO(In “external mode", run programmed operation)
34
RES_E (External reset, valid only when alarm.)
35
MPO (In “external mode” run manual cycle operation.)