Protection parameter group 06
PARAMETER DESCRIPTION 109
5.7.3 Over torque detection
Output current detection function can be used for over torque detection.
Parameter
Name
Default Setting Range
Content
06-08
P.155
Over torque detection
level
0.0%
0
No over torque detection.
0.1~200%
Over torque detection.
06-09
P.156
Over torque detection
time
1.0s
0~60.0s
---
06-10
P.260
Action when detect
over torque
1
0
OL2 alarm will not be reported after over torque detection,
and inverter keeps running.
1
OL2 alarm will be reported after over torque detection, and
inverter stops.
Over torque detection
If set value of 06-08(P.155) is not zero, over-torque detection function is on.
If output current exceeds over-torque detection level (06-08(P.155)) and over-torque detection time (06-09(P.156)),
inverter will trigger OL2 alarm and stop. If relay output terminals A-C(03-11(P.85))
is
set to over-torque alarm (set
value is 12), inverter will output a signal.
If relay output terminals A-C (03-11(P.85))is set to over-load alarm (set
value is 3), and 06-10 (P.260) =1, inverter will output a signal.
Please refer to Chapter 5 03-11(P.85) for details.
100%
06-08
(
P.155)
Inverter full load current level
O
ut
pu
t c
ur
re
nt
(
%
)
Time
Output
06-09
(P.156)
OL(Overload
alarm
)
Reset signal
Inverter alarm OL2
and stop outputting
Setting