Electric specification
INVERTER INTRODUCTION 13
3.1.2 220V series single phase
Frame
A
B
Model SL3-021-□□□K-□□
0.4
0.75
1.5
2.2
Inverter
Output
Rated output capacity (kVA)
1
1.5
2.5
4.2
Rated output current (A)
2.7
4.5
8
11
Applicable motor capacity (HP)
0.5
1
2
3
Applicable motor capacity (kW)
0.4
0.75
1.5
2.2
Overload current rating
150% 60 seconds, 200% 1 seconds (inverse-time characteristics)
Carrier frequency (kHz)
1~15kHz
Maximum output voltage
3 phase 200-240V
Power
Supply
Rated input current (A) *Note 1
6.5
9.3
15.7
24
Rated input AC voltage/ frequency
single phase 200-240V 50Hz/60Hz
Permissible AC voltage fluctuation
single phase 170-264V 50Hz/60Hz
Permissible frequency fluctuation
±5%
Power supply capacity (kVA)
1.5
2.5
3.5
6.4
Cooling method
Fan cooling
Weight (kg)
0.6
0.6
0.6
0.8
Note 1: The value indicates the current at rated output. The rated input current value is not only affected by power
transformer, input side reactor, wiring condition, but also fluctuates with the impedance of the power supply side.