Terminal wire arrangement
INVERTER INTRODUCTION 28
(2) Insert the wire to blade terminal and crimping.
Insert wires to a blade terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve.
Check the condition of the blade terminal after crimping. Do not use a blade terminal of which the crimping is
inappropriate, or the face is damaged.
Please do use blade terminals with insulation sleeve. Blade terminals commercially available:
Cable gauge (mm²) Blade terminals
model
L (mm)
d1 (mm)
d2 (mm)
Manufacturer
Crimping tool
product number
0.3
AI 0,25-6 WH
10.5
0.8
2
Phoenix
Contact
Co., Ltd.
CRIMPFOX 6
0.5
AI 0,5-6 WH
12
1.1
2.5
0.75
AI 0,75-6 GY
12
1.3
2.8
0.75
(for two wires)
AI-TWIN
2×0,75-6 GY
12
1.3
2.8
Note:1. Please Use a small flathead screwdriver (tip thickness: 0.6mm, width: 3.0mm). If a flathead screwdriver
with a narrow tip is used, terminal block maybe damaged.
2. Tightening torque is 20~25kgf.cm too large tightening torque can cause screw slippage, too little tightening
torque can cause a short circuit or malfunction.
Toggle switch
Switch number
Switch
state
Explanation
Remarks
AVI/ACI
*
Input 4~20mA current signal into terminal 3
Also requires setting 02-20(P.17), refer
to chapter 5.3.3
Input 0~10V voltage signal into terminal 3
Note: 1. The state with “ * ” mark is the default state.
0~0.5mm