PID parameter group 08
PARAMETER DESCRIPTION 130
5.9 PID parameter group 08
Group
Parameter
number
Name
Setting range
Default Page
08-00
P.170
PID function selection
0: Off
0
2:Parameter 08-03(P.225) as target value, terminal 3-5
current/voltage input as feedback source
08-01
P.171
PID feedback control
method
0: Negative feedback control.
0
1: Positive feedback control.
08-03
P.225
PID target value from
keypad
0~08-43(P.251)
20.0%
08-04
P.172
Proportional gain
1~100
20
08-05
P.173
Integral time
0~100.0s
1.0s
08-06
P.174
Differential time
0~10000ms
0ms
08-07
P.175
Abnormal deviation
0~100.0%
0.0%
08-08
P.176
Abnormal duration time
0~600.0s
30.0s
08-09
P.177
Abnormal processing mode
0: Stop freely
0
1: Slow down to stop
2: Alarm and continue operation
08-10
P.178
Sleep detection deviation
0~100.0%
0.0%
08-11
P.179
Sleep detection duration
time
0~255.0s
1.0s
08-12
P.180
Wake-up level
0~100.0%
90.0%
08-13
P.181
Stop level
0~120.00Hz
40.00Hz
08-14
P.182
Upper integral limit
50Hz system:0~120.00Hz
50.00Hz
60Hz system:0~120.00Hz
60.00Hz
08-15
P.183
Deceleration step length
when stable
0~10.00Hz
0.50Hz
08-18
P.223
Analog feedback signal bias 0~100.0%
0.0%
08-19
P.224
Analog feedback signal
gain
0~100.0%
100.0%
08-43
P.251
PID pressure range (Bar)
setting
1.0~100.0
100.0
08-45
P.253
Analog signal feedback loss
detection time
0~600.0
0.0 s
08-46
P.254
Analog signal feedback loss
action selection
0:Alarm AErr and inverter stop freely
0
1:Slow down to stop then alarm AErr
2:Alarm AErr and continue operation