Basic operation steps for different modes
BASIC OPERATION 39
4.3.7 Basic operation steps for combined mode 3(00-16(P.79)=6)
Step
Description
1
• In Combined Mode 3, indicator in
will flicker.
Note: 1. For detailed operation procedures for monitor mode, please refer to section 4.2.
2
Default priority from high to low:
• When external JOG is “on”, target frequency is determined by 01-13(P.15). Acceleration / deceleration time is set by the
value of 01-14(P.16).
• When RL, RM, RH and REX of multi-speed stage levels are “on”, target frequency is determined by combination of
multi-speed stage levels, please refer to section 5.5.1 16 step speed.
• Target frequency is set by communication.
3
• Give STF/STR signal to run the motor. At this point, indicator
will flicker to indicate that the motor is running.
• Functions of 00-02(P.996~P.999) can be accomplished by communication.
Note: For detailed operation procedures for the monitor mode, please refer to Section
4
• When terminal STF/STR signals turn off, motor will decelerate until it comes to a full stop.
• Indicator in
will not turn off until the inverter stops outputting.
4.3.8 Basic operation steps for combined mode 4(00-16(P.79)=7)
Step
Description
1
•In Combined Mode 4, indicator in
will flicker.
Note: 1. For detailed operation procedures for monitor mode, please refer to Section 4.2
.
2
Default priority from high to low:
• If target frequency is set by multi-speed stage levels, please refer to section 5.5.1 16 step speed.
• If target frequency is set by input signal across terminal 3-5, please refer to section 5.3.3 terminal 3-5 signal selection
and processing .
3
•The inverter starting is activated by communication (including “Reset”). At this point, indicator
will flicker indicating
that the motor is running.
Note: 1. For detailed operation procedures for the monitoring mode, please refer to Section 4.2.3.
2. While the motor is running, the user can enter into the frequency setting mode to change the target frequency for
regulating the motor speed.
4
• When communication sends the stop instruction, the motor will decelerate until it comes to a full stop.
• Indicator
will not turn off until the inverter stops the output.
4.3.9
Basic operation steps for combined mode 5(00-16(P.79)=8)
Step
Description
1
• In Combined Mode 5, indicator
will light up.
Note: For detailed operating procedures for monitor mode, please refer to Section 4.2.
2
•Target frequency of the inverter is set by keypad:
• When RL, RM, RH and REX for multi-speed stage levels are “on”, target frequency is determined by the combination of
multi-speed stage levels , please refer to section 5.5.1 16 step speed.
• When external JOG is “on”, target frequency is determined by 01-13(P.15). Acceleration / deceleration time is set by the
value in 01-14(P.16).
3
•Inverter starting is triggered by external STF or STR terminals.
Note: 1. For detailed operation procedures for the monitoring mode, please refer to section 4.2.3.
2. While the motor is running, the user can enter frequency setting mode to change the target frequency for
regulating motor speed.
4
• When terminal STF/STR signals turn off, motor will decelerate until it comes to a full stop.
• Indicator in
will not turn off until the inverter stops outputting.