Date _______________
Date Code 20060320
Instruction Manual
SEL-311C Relay
SET.5 of 6
SEL-311C Settings Sheet Application Setting 221F
Parity (Odd [O], Even [E], or None [N])
(This setting is available when PROTO = SEL or LMD.)
PARITY
=
Stop Bits (1, 2)
(This setting is available when PROTO = SEL or LMD.)
STOP
=
Other Port Settings (See Below)
Time-out (0–30 minutes)
T_OUT
=
DTA Meter Format (Y, N)
DTA
=
Send auto messages to port (Y, N)
AUTO
=
Enable hardware handshaking (Y, N, MBT)
(MBT is available when PROTO = MBA or MBB.)
RTSCTS
=
Fast Operate Enable (Y, N)
FASTOP
=
OTHER PORT SETTINGS
Set T_OUT to the number of minutes of serial port inactivity for an automatic
log out. Set T_OUT = 0 for no port time-out. This setting is available when PROTO = SEL or LMD.
Set DTA = Y to allow an SEL-DTA or SEL-DTA2 to communicate with the relay. This setting is
available when PROTO = SEL or LMD.
Set AUTO = Y to allow automatic messages at the serial port. This setting is available when
PROTO = SEL or LMD.
Set RTSCTS = Y to enable hardware handshaking. With RTSCTS = Y, the relay will not send
characters until the CTS input is asserted. Also, if the relay is unable to receive characters, it
deasserts the RTS line. Setting RTSCTS is not applicable to serial Port 1 (EIA-485) or a port
configured for SEL Distributed Port Switch Protocol.
Set FASTOP = Y to enable binary Fast Operate messages at the serial port. Set FASTOP = N to block
binary Fast Operate messages. Refer to
Appendix D: Configuration, Fast Meter, and Fast Operate
for the description of the SEL-311C Relay Fast Operate commands. This setting is
available when PROTO = SEL or LMD.
Power System Configuration (See
Settings Explanations on page 9.33
)
Phase rotation (ABC, ACB)
PHROT
=
Nominal frequency (50 Hz, 60 Hz)
NFREQ
=
Display Point Labels (See
Rotating Default Display (Only on Models With LCD) on
and
Rotating Default Display on page 11.12
)
NOTE:
This application assumes that the user has programmed the text settings as indicated below.
If the text settings listed below are not programmed as indicated, the front-panel display points will
not display the correct information for these display points.
Display if DP1 = logical 1 (16 characters)
DP1_1
= BREAKER CLOSED
Display if DP1 = logical 0 (16 characters)
DP1_0
= BREAKER OPEN
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...