5.4
SEL-311C Relay
Instruction Manual
Date Code 20060320
Trip and Target Logic
Trip Logic
With this setting, the
OPEN
command can provide a trip only if optoisolated
input
IN105
is asserted. This is just one
OPEN
command supervision
example—many variations are possible.
To prevent the execution of the
OPEN
command from initiating reclosing,
include Relay Word bit OC in the SEL
OGIC
control equation setting 79DTL
(Drive-to-Lockout).
A
COMM
target LED option for the
OPEN
Panel Target LEDs on page 5.31
Unlatch Trip
Once Relay Word bit TRIP is asserted to logical 1, it remains asserted at
logical 1 until
all
the following conditions come true:
➤
Minimum Trip Duration Timer stops timing (logic output of the
TDURD timer goes to logical 0)
➤
Output of OR-1 gate in
deasserts to logical 0
➤
One of the following occurs:
➢
SEL
OGIC
control equation setting ULTR asserts to
logical 1,
➢
The front-panel
{TARGET RESET}
pushbutton is pressed,
➢
Or the
TAR R
(Target Reset) command is executed via
the serial port.
The front-panel
{TARGET RESET}
pushbutton and the
TAR R
(Target Reset)
serial port command are primarily used during testing. Use these to force the
TRIP Relay Word bit to logical 0 if test conditions are such that setting ULTR
does not assert to logical 1 to automatically deassert the TRIP Relay Word bit.
Other Applications for the Target Reset Function
Note that the combination of the
{TARGET RESET}
pushbutton and the
TAR R
(Target Reset) serial port command is also available as Relay Word bit
TRGTR. See
and accompanying text for applications for Relay
Word bit TRGTR.
Factory Settings
Example (Using
Setting TR)
In this example the “communications-assisted” and “switch-onto-fault” trip
logic at the top of
OGIC
control equation trip
setting TR is now the only input into OR-1 gate and flows into the “seal-in and
unlatch” logic for Relay Word bit TRIP.
The factory settings for the trip logic SEL
OGIC
control equation settings are:
TR =
M1P + Z1G + M2PT + Z2GT + 51GT + 51QT + OC
(trip conditions)
ULTR =
!(50L + 51G)
(unlatch trip conditions)
The factory setting for the Minimum Trip Duration Timer setting is:
TDURD =
9.000 cycles
See the settings sheets in
for setting ranges.
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...