5.34
SEL-311C Relay
Instruction Manual
Date Code 20060320
Trip and Target Logic
Front-Panel Target LEDs
DP3_1 =
BREAKER FAILURE
DP3_0 =
(blank)
Figure 5.17
Seal-in of Breaker Failure Occurrence for Message Display
If a breaker failure trip has occurred, the momentary assertion of SV7T
(breaker failure trip) will cause SV8 in
to seal in. Asserted SV8 in
turn asserts DP3, causing the message:
to display in the rotating default display.
This message can be removed from the display rotation by pushing the
{TARGET RESET}
pushbutton (Relay Word bit TRGTR pulses to logical 1,
unlatching SV8 and in turn deasserting DP3). Thus, front-panel rotating
default displays can be easily reset along with the front-panel targets by
pushing the
{TARGET RESET}
pushbutton.
SV7T
Breaker Failure Trip
(= logical 1)
(= logical 0)
Target Reset
TRGTR
SV8
DP3 = SV8
DP3_1 = BREAKER FAILURE
DP3_0 = (blank)
BREAKER FAILURE
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...