Instruction Manual
SEL-311C Relay
Distance, Out-of-Step, Overcurrent, Voltage, Synchronism Check, and Frequency Elements
Distance Elements
Note 1: xAG = A-Phase to Ground Reactance Calculation, XG1 = Zone 1 Reactance Setting, X1 = Zone 1 Extension
u
,
rAG = A-Phase to Ground Resistance Calculation, RG1 = Zone 1 Resistance Setting.
q
w
from
;
e
from
;
r
from
;
t
;
y
from
u
Figure 3.10
Zone 1 Quadrilateral Ground Distance Logic
|IA|
50L1
(Setting)
_
+
_
+
|IG|
50GZ1
(Setting)
xAG < XG1 • X1
FSA
r
3PO
t
ILOP
VPOLV
Zone 1 A-Phase Quadrilateral Ground Distance Logic.
B- and C-Phase Logic Is Similar.
–RG1 < rAG < RG1
w
32QGE
e
32GF
XGPOL = I2
(Advanced Setting)
XGPOL = IG
(Advanced Setting)
q
32VE
y
CVTBL
XAG1
See Note 1
Relay
Word
Bits
(unless
noted)
Relay
Word
Bit
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...