12.2
SEL-311C Relay
Instruction Manual
Date Code 20060320
Standard Event Reports and SER
Standard 15/30/60/180-Cycle Event Reports
Standard 15/30/60/180-Cycle Event Reports
for an example event report.
Event Report
Length (Settings
LER and PRE)
The SEL-311C provides user-programmable event report length and pre-fault
length. Event report length is 15, 30, 60 or 180 cycles. Pre-fault length ranges
from 1 to 179 cycles. Pre-fault length is the first part of the event report that
precedes the event report triggering point.
Set the event report length with the SET G LER setting. Set the pre-fault
length with the SET G PRE setting. See the
SET G
Global Settings (Serial Port Command SET G and Front Panel) on
page SET.22
for instructions on setting the LER and PRE settings.
Changing the LER setting erases all events stored in nonvolatile memory.
Changing the PRE setting has no effect on the nonvolatile reports.
Standard Event
Report Triggering
The relay triggers (generates) a standard event report when any of the
following occur:
➤
Relay Word bit TRIP asserts
➤
Programmable SEL
OGIC®
control equation setting ER asserts
➤
TRI
(Trigger Event Reports) serial port command executed
➤
Output contacts
OUT101
–
OUT107
(Models 311C00
x
and
311C01
x
) pulsed via the serial port or front-panel
PUL
(Pulse
output contact) command
Relay Word Bit TRIP
. If Relay Word bit TRIP asserts to logical 1, an event
report is automatically generated. Any trip condition that asserts in setting TR
causes the TRIP Relay Word bit to assert immediately. The Relay Word bit
TRIP asserts, and an event report is automatically generated. Any condition
that causes a trip does
not
have to be entered in SEL
OGIC
control equation
setting ER.
Relay Word bit TRIP (in
) is usually assigned to an output contact
for tripping a circuit breaker (e.g., SEL
OGIC
control equation setting OUT101
= TRIP).
Programmable SEL
OGIC
Control Equation Setting ER
The programmable SEL
OGIC
control equation event report trigger setting ER
is set to trigger standard event reports for conditions other than trip conditions.
When setting ER sees a logical 0 to logical 1 transition, it generates an event
report (if the SEL-311C is not already generating a report that encompasses
the new transition). The factory setting is:
ER =
/M2P + /Z2G + /51G + /51Q + /50P1 + /LOP
NOTE
:
is on multiple
pages.
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...