3.2
SEL-311C Relay
Instruction Manual
Date Code 20060320
Distance, Out-of-Step, Overcurrent, Voltage, Synchronism Check, and Frequency Elements
Distance Elements
shows the different calculations used for the positive-sequence
polarized mho elements and compensator-distance mho elements. Notice that
the positive-sequence polarized mho element equation is the solution of
for the quantity “|Z|,” which represents the relay reach at the
balance point. This equation is in the form of a line drop-compensated voltage
and a polarizing (reference) voltage.
Equation 3.1
As mentioned previously, a digital relay mho element tests the angle between
a line drop-compensated voltage and a polarizing (reference) voltage.
through
show the operating voltages “inside” positive-
sequence polarized mho elements and compensator-distance mho elements.
Note that V1mem is the polarizing voltage for the positive-sequence polarized
mho element and (Z • I – V) is the line drop-compensated voltage. In the
compensator distance phase-to-phase element, the polarizing voltage is the
unfaulted phase-to-phase voltage, and the line drop-compensated voltage is
the faulted phase-to-phase voltage. In the compensator distance three-phase
element, the polarizing voltage is (–jV
AB
– 0.25 • V
C
mem) and the line drop
compensated voltage is (V
AB
– Z • I
AB
).
0
Re
Z
I
V
–
•
(
)
Vmem
*
•
[
]
=
Table 3.1
Phase Distance Calculations
Positive-Sequence
Polarized Mho Element
Compensator-Distance Mho Element
Phase A-B
Phase-to-Phase Element
Phase B-C
Three-Phase Element
Phase C-A
Z
Re
V
AB
V
AB
mem*
•
(
)
Re 1
Z
I
AB
V
AB
mem*
• •
∠
(
)
----------------------------------------------------------------------
=
mPP
Im V
AB
Z
–
I
AB
•
(
)
•
V
BC
Z
I
BC
•
–
(
)
*
[
]
=
Z
Re
V
BC
V
BC
mem*
•
(
)
Re 1
Z
I
BC
V
BC
mem*
• •
∠
(
)
-----------------------------------------------------------------------
=
mABC
Im V
AB
Z
–
I
AB
•
(
)
•
jV
–
AB
0.25
V
C
mem
•
–
(
)
*
[
]
=
Z
Re
V
CA
V
C A
mem*
•
(
)
Re 1
Z
I
C A
V
C A
mem*
• •
∠
(
)
-----------------------------------------------------------------------
=
mPP
Phase-to-phase torque calculation.
=
Positive torque restrains,
negative torque operates.
Z
Impedance measurement
=
at the line angle.
mABC
Three-phase torque calculation.
=
Positive torque restrains,
negative torque operates.
Z
Replica line impedance at
=
operating or balance point.
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...