D.11
Date Code 20060320
Instruction Manual
SEL-311C Relay
Configuration, Fast Meter, and Fast Operate Commands
Message Definitions
It is common practice to route remote bits to output contacts to provide remote
control of the relay outputs. If you wish to pulse an output contact closed for a
specific duration, SEL recommends using the remote bit pulse command and
SEL
OGIC®
control equations to provide secure and accurate contact control.
The remote device sends the remote bit pulse command; the relay controls the
timing of the output contact assertion. You can use any remote bit (RB1
through RB16), and any SEL
OGIC
control equation timer (SV1 through SV16)
to control any of the output contacts (
OUT101
through
OUT108
). For example, to
pulse output contact
OUT104
for 30 cycles with Remote Bit RB4 and SEL
OGIC
control equation timer SV4, issue the following relay settings:
via the
SET L
command,
SV4 =
RB4
SV4 input is RB4
OUT104 =
SV4T
route SV4 timer output to OUT104
via the
SET
command,
SV4PU =
0
SV4 pickup time = 0
SV4DO =
30
SV4 dropout time is 30 cycles
To pulse the contact, send the
A5E006430DDB
command to the relay.
A5E3 Fast Operate
Breaker Control
The external device sends the message shown in
to perform a fast
breaker open/close.
The relay performs the specified breaker operation if the following conditions
are true:
1. Conditions 1–5 defined in the A5E0 message are true.
2. The breaker jumper (JMP2B) is in place on the SEL-311C
main board.
A5CD Fast Operate
Reset Definition
Block
In response to an A5CD request, the relay sends the configuration block
shown in
for the Fast Operate Reset message.
Table D.10
A5E3 Fast Operate Breaker Control
Data
Description
A5E3
Command
06
Length
1 byte
Operate code:
31–OPEN breaker
11–CLOSE breaker
1 byte
Operate Validation: 1 + (Operate code • 4)
checksum
1-byte checksum of preceding bytes
Table D.11
A5CD Fast Operate Reset Definition Block
(Sheet 1 of 2)
Data
Description
A5CD
Command
0E
Message length
01
The number of Fast Operate reset codes supported
00
Reserved for future use
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...