7.6
SEL-311C Relay
Instruction Manual
Date Code 20060320
Inputs, Outputs, Timers, and Other Control Logic
Optoisolated Inputs
79DTL =
!IN102 + ...
= NOT(IN102) + ... = NOT(logical 1) +... = logical 0 +
...
Section 6: Close and Reclose Logic
for more information on SEL
OGIC
control equation setting 79DTL.
The pickup/dropout timer for input
IN102
(IN102D) in this example might be
set at:
IN102D =
1.00 cycle
to provide input energization/de-energization debounce.