3.36
SEL-311C Relay
Instruction Manual
Date Code 20060320
Distance, Out-of-Step, Overcurrent, Voltage, Synchronism Check, and Frequency Elements
Time-Overcurrent Elements
The Torque Control Switch closes and phase time-overcurrent element
51PT is enabled and nondirectional.
51PTC =
M2P
The 51P/51PT uses the Zone 2 mho phase distance element to provide
forward directional control.
Other SEL
OGIC
control equation torque control settings may be set to provide
directional control. See
Overcurrent Directional Control Provided by Torque
Reset Timing Details (51PT Element Example)
.
Any time current I
ABC
goes above pickup setting 51PP and the phase time-
overcurrent element starts timing, Relay Word bit 51PR (reset indication) =
logical 0. If the phase time-overcurrent element times out on its curve, Relay
Word bit 51PT (curve time-out indication) = logical 1.
Setting 51PRS = Y
If electromechanical reset timing setting 51PRS = Y, the phase time-
overcurrent element reset timing emulates electromechanical reset timing. If
maximum phase current, I
ABC
, goes above pickup setting 51PP (element is
timing or already timed out) and then current I
ABC
goes below 51PP, the
element starts to time to reset, emulating electromechanical reset timing.
Relay Word bit 51PR (resetting indication) = logical 1 when the element is
fully reset. See
Time-Overcurrent Curves on page 9.5
for reset curve
equations.
Setting 51PRS = N
If reset timing setting 51PRS = N, element 51PT reset timing is a 1-cycle
dropout. If current I
ABC
goes above pickup setting 51PP (element is timing or
already timed out) and then current I
ABC
goes below pickup setting 51PP,
there is a 1-cycle delay before the element fully resets. Relay Word bit 51PR
(reset indication) = logical 1 when the element is fully reset.
Residual Ground
Time-Overcurrent
Element
To understand the operation of
, follow the explanation given for
, substituting residual ground current I
G
(I
G
= 3I
0
= I
A
+ I
B
+ I
C
)
for maximum phase current I
ABC
and substituting like settings and Relay
Word bits.
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...