7.11
Date Code 20060320
Instruction Manual
SEL-311C Relay
Inputs, Outputs, Timers, and Other Control Logic
Remote Control Switches
Remote Control Switches
Remote control switches are operated via the serial communications port only
(see
CON Command (Control Remote Bit) on page 10.37
The switch representation in this figure is derived from the standard:
Graphics Symbols for Electrical and Electronics Diagrams IEEE Std 315-1975,
CSA Z99-1975, ANSI Y32.2-1975, 4.11 Combination Locking and Nonlocking Switch,
Item 4.11.1.
Figure 7.10
Remote Control Switches Drive Remote Bits RB1 Through RB16
The outputs of the remote control switches in
are Relay Word bits
RB
n
(
n
= 1–16), called remote bits. Use these remote bits in SEL
OGIC
control
equations.
Any given remote control switch can be put in one of the following three
positions:
➤
ON (logical 1)
➤
OFF (logical 0)
➤
MOMENTARY (logical 1 for one processing interval)
Remote Bit
Application Ideas
With SEL
OGIC
control equations, the remote bits can be used in applications
similar to those that local bits are used in (see
).
Also, remote bits can be used much as optoisolated inputs are used in
operating latch control switches (see discussion following
). Pulse
(momentarily operate) the remote bits for this application.
Remote Bit States
Not Retained When
Power Is Lost
The states of the remote bits (Relay Word bits RB1–RB16) are not retained if
power to the relay is lost and then restored. The remote control switches
always come back in the OFF position (corresponding remote bit is deasserted
to logical 0) when power is restored to the relay.
Remote Bit States
Retained When
Settings Changed or
Active Setting Group
Changed
The state of each remote bit (Relay Word bits RB1–RB16) is retained if relay
settings are changed (for the active setting group or one of the other setting
groups) or the active setting group is changed. If a remote control switch is in
the ON position (corresponding remote bit is asserted to logical 1) before a
setting change or an active setting group change, it comes back in the ON
position (corresponding remote bit is still asserted to logical 1) after the
change. If a remote control switch is in the OFF position (corresponding
Logical 1
RBn
(n = 1 through 16)
ON Position
(Maintained Logical 1
Position)
OFF Position
(Maintained Logical 0 Position)
MOMENTARY Position
(Logical 1 for One Processing Interval)
Relay
Word
Bit
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...