9.22
SEL-311C Relay
Instruction Manual
Date Code 20060320
Setting the Relay
Relay Word Bits (Used in SEL
OGIC
Control Equations)
15
MAB1
Mho AB phase distance zone 1, instantaneous (see
Testing
MBC1
Mho BC phase distance zone 1, instantaneous (see
)
MCA1
Mho CA phase distance zone 1, instantaneous (see
MAB2
Mho AB phase distance zone 2 instantaneous (see
MBC2
Mho BC phase distance zone 2, instantaneous (see
)
MCA2
Mho CA phase distance zone 2, instantaneous (see
CVTBL
CCVT transient blocking logic active (see
Indication, Testing
SOTFT
Switch-onto-fault trip
16
MAG1
Mho ground distance A-phase, zone 1 (see
)
Testing
MBG1
Mho ground distance B-phase, zone 1 (see
MCG1
Mho ground distance C-phase, zone 1 (see
MAG2
Mho ground distance A-phase, zone 2 (see
)
MBG2
Mho ground distance B-phase, zone 2 (see
MCG2
Mho ground distance C-phase, zone 2 (see
DCHI
Station dc battery
instantaneous overvoltage element (see
Indication
DCLO
Station dc battery
instantaneous undervoltage element (see
17
BCW
BCWA + BCWB + BCWC
BCWA
A-phase breaker contact wear has reached 100% wear level (see
BCWB
B-phase breaker contact wear has reached 100% wear level (see
BCWC
C-phase breaker contact wear has reached 100% wear level (see
FIDEN
Fault Identification Logic Enabled
Internal control
FSA
A-phase to ground or B-C phases to ground fault
identification logic output used in distance element logic
FSB
B-phase to ground or A-C phases to ground fault
identification logic output used in distance element logic
FSC
C-phase to ground or A-B phases to ground fault
identification logic output used in distance element logic
18
SG1
Setting group 1 active (see
)
Indication
SG2
Setting group 2 active (see
)
SG3
Setting group 3 active (see
)
SG4
Setting group 4 active (see
)
SG5
Setting group 5 active (see
)
SG6
Setting group 6 active (see
)
OC
Asserts 1/4 cycle for Open Command execution
(see
OPE Command (Open Breaker) on page 10.36
)
Control
CC
Asserts 1/4 cycle for Close Command execution
(see
CLO Command (Close Breaker) on page 10.34
Table 9.6
Relay Word Bit Definitions for the SEL-311C
(Sheet 6 of 16)
Row
Bit
Definition
Primary Application
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...