B.4
SEL-311C Relay
Instruction Manual
Date Code 20060320
Firmware Upgrade Instructions
If the computer settings do not match the relay settings,
change the computer settings to match the relay
settings.
b. Click
OK
.
Figure B.3
Determining Communications Parameters for the Computer
Step 7. Set the terminal emulation to VT100:
a. From the
File
menu, choose
Properties
.
b. Select the
Settings
tab in the
Firmware Upgrade
Properties
dialog box (
).
c. Select
VT100
from the
Emulation
list box and click
OK
.
Figure B.4
Setting Terminal Emulation
Step 8. Confirm serial communication.
Press
<Enter>
. In the terminal emulation window, you should
see the Access Level 0 = prompt, similar to that in
.
If this is successful, proceed to
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...